ZW32-40.5F (M) outdoor high-voltage intelligent (permanent magnet) vacuum circuit breaker
Project-focused selection
Quality-controlled supply
Export service
Overview
The ZW32-40.5F(M) outdoor high-voltage intelligent (permanent magnet) vacuum circuit breaker mainly consists of integrated solid-sealed poles, a current transformer, an operating mechanism, and a housing. A disconnecting switch can be added. This model of circuit breaker features a miniaturized design with a high-quality steel housing. The current transformer can be selected according to user needs.
This device is mainly used in medium-voltage overhead power grids for switching on and off load currents, overload currents, and short-circuit currents.
Model Meaning

Usage conditions
◆Ambient air temperature: -30℃~+60℃;
◆Altitude: Not exceeding 3000 meters;
◆Wind speed not exceeding 34m/s;
◆Vibrations or ground movements from outside the switching and control equipment are negligible;
◆Soiliness level: IV;
◆Storage temperature: -40℃ ~ +85℃.
Main technical parameters
Main technical parameters of circuit breaker
| Project | Unit | Parameter |
| Rated voltage | kV | 40.5 |
| Rated current | A | 1250/1600 |
| Rated frequency | HZ | 50 or 60 |
| Power frequency withstand voltage 1min (wet) (dry) phase-to-phase, to ground/break | kV | 81 |
| Lightning impulse withstand current (peak value) phase-to-phase, to ground/break | kV | 185 |
| Rated short-circuit breaking current | kA | 25/31.5 |
| Rated short-circuit making current (peak value) | kA | 63/80 |
| Rated peak withstand current | kA | 63/80 |
| 4S Short-Time Withstand Current | kA | 25/31.5 |
| Rated operating cycle | Split – 0.1s – Combine – 3s – Platform – 6s – Combine – 60s – Restore | |
| Rated short-circuit current breaking times | 次 | 30 |
| Mechanical life | 次 | 10000 |
| Mechanism control voltage | V | AC/DC220 |
| Secondary circuit 1min power frequency withstand voltage | kV | 2 |
Main technical parameters
Main technical parameters of circuit breakers
| Project | Unit | Parameter |
| Contact gap | mm | 16±1 |
| Contact overtravel | mm | 4±0.5 |
| Opening speed | m/s | 1.4-1.8 |
| Closing speed | m/s | 0.4-0.8 |
| Contact closing bounce time | ms | ≤5 |
| Inter-phase center distance | mm | 460±2 |
| Asynchronous opening and closing of three-phase circuit breakers | ms | ≤2 |
| Resistance of each phase conductive circuit | μΩ | <80 |
| Closing time | ms | ≤ 100 |
| Opening time | ms | ≤ 50 |
| Weight | Kg | 270 |
External dimensions and installation dimensions (mm)

Selecting ZW32-40.5F (M) Permanent Magnet Vacuum Circuit Breaker
Before requesting a quotation, confirm system voltage, current and fault duty, operating mechanism and control interface and mounting dimensions and service environment. Send the exact model, quantity and installation details so the configuration and document set can be checked against your project.
Compare the vacuum circuit breakers range, including AB-3S-40.5 Outdoor Pole-mounted Permanent Magnetic Vacuum Circuit Breaker; ZW20-12F (M) outdoor high voltage intelligent (permanent magnet) vacuum circuit breaker. For drawings and order-specific questions, send your product requirements to GRL.