The FZN25 and FZRN25 series vacuum load switches and combined electrical appliances are suitable for load control and short-circuit protection in three-phase AC 50Hz ring networks or terminal power supplies and industria

Project-focused selection

Support matched to operating conditions and project requirements.

Quality-controlled supply

Clear communication from confirmation through delivery.

Export service

Documentation and shipping support for overseas buyers.

Overview

The FZN25 and FZRN25 series vacuum load switches and combined electrical appliances are suitable for load control and short-circuit protection in three-phase AC 50Hz ring networks or terminal power supplies and industrial electrical equipment. The load switches connect and disconnect loads, closed-loop current, and unloaded transformer and cable charging current. The combined electrical appliances can interrupt any current up to the rated short-circuit current. They employ direct-acting isolation contacts and vacuum arc chamber linkage. Both manual and electric functions are available.

The unique transmission structure design of FZN25 and FZRN25 ensures that the arc-extinguishing chamber only bears high pressure at the moment of closing and opening, resulting in a small size and light weight. FZN25 and FZRN25 can achieve one-time operation of the isolation break and the arc-extinguishing chamber break.

The FNZ25 and FZRN25 have a grounding valve between the stationary contact and the conductive cylinder of the moving contact, which is linked to the grounding switch, ensuring both safety and convenient maintenance.

Model Meaning

FZN25-12/FZRN25-12 Vacuum Load Switch

FZN25-12/FZRN25-12 Vacuum Load Switch

Main technical parameters

Project Unit Parameter
FZN25-12D/T630-20 FZRN25-12D/T125-31.5
Rated voltage kV 12
Rated frequency HZ 50
Rated current A 630 125
Rated insulation level 1-minute power frequency withstand voltage kV Arc-extinguishing chamber fracture 30; to ground, phase-to-phase 42; isolation fracture 48
Lightning impulse withstand voltage kV Ground-to-ground, phase-to-phase 75: isolation break 85
Rated dynamic current (peak) KA 50 –
4S thermally stable current KA 20 –
Rated active load breaking current A 630 125
Rated closed-loop breaking current A 630 125
Rated cable charging breaking current A 10 10
Breaking off no-load transformer capacity kVA 1250 1250
Rated short-circuit breaking current KA – 31.5
Rated transfer current, rated handover current A – 2000
Fuse model – SDLAJ-12 SFLAJ-12
Impactor output energy J – 2-5(中等)
Rated short-circuit making current KA 50
Rated dynamic stability current of grounding switch KA 50
Grounding switch 2S thermal stability current KA 20
Auxiliary circuit rated voltage V AC/CD :220/110
Mechanical life 次 10000

FZRN25-12D/125-31.5 Vacuum Load Switch-Fuse Combination Appliance Outline and Installation Dimensions (mm)