Get a Quote
Home / Products / Indoor High-Voltage / High Voltage Circuit Breaker / Vacuum Circuit Breakers / ZW32-40.5F (M) outdoor high-voltage intelligent (permanent magnet) vacuum circuit breaker
Vacuum Circuit Breakers

ZW32-40.5F (M) outdoor high-voltage intelligent (permanent magnet) vacuum circuit breaker

The ZW32-40.5F(M) outdoor high-voltage intelligent (permanent magnet) vacuum circuit breaker mainly consists of integrated solid-sealed poles, a current transformer, an operating mechanism, and a housing. A disconnecting

Project-focused selection

Support matched to operating conditions and project requirements.

Quality-controlled supply

Clear communication from confirmation through delivery.

Export service

Documentation and shipping support for overseas buyers.

Overview

The ZW32-40.5F(M) outdoor high-voltage intelligent (permanent magnet) vacuum circuit breaker mainly consists of integrated solid-sealed poles, a current transformer, an operating mechanism, and a housing. A disconnecting switch can be added. This model of circuit breaker features a miniaturized design with a high-quality steel housing. The current transformer can be selected according to user needs.

This device is mainly used in medium-voltage overhead power grids for switching on and off load currents, overload currents, and short-circuit currents. 

Model Meaning

ZW32-40.5F (M) outdoor high-voltage intelligent (permanent magnet) vacuum circuit breaker

Usage conditions

◆Ambient air temperature: -30℃~+60℃;

◆Altitude: Not exceeding 3000 meters;

◆Wind speed not exceeding 34m/s;

◆Vibrations or ground movements from outside the switching and control equipment are negligible;

◆Soiliness level: IV;

◆Storage temperature: -40℃ ~ +85℃.

Main technical parameters

Main technical parameters of circuit breaker

Project Unit Parameter
Rated voltage kV 40.5
Rated current A 1250/1600
Rated frequency HZ 50 or 60
Power frequency withstand voltage 1min (wet) (dry) phase-to-phase, to ground/break kV 81      
Lightning impulse withstand current (peak value) phase-to-phase, to ground/break kV 185
Rated short-circuit breaking current kA 25/31.5
Rated short-circuit making current (peak value) kA 63/80
Rated peak withstand current kA 63/80
4S Short-Time Withstand Current kA 25/31.5
Rated operating cycle Split – 0.1s – Combine – 3s – Platform – 6s – Combine – 60s – Restore
Rated short-circuit current breaking times 次 30
Mechanical life 次 10000
Mechanism control voltage V AC/DC220
Secondary circuit 1min power frequency withstand voltage kV 2

Main technical parameters

Main technical parameters of circuit breakers

Project Unit Parameter
Contact gap mm 16±1
Contact overtravel mm 4±0.5
Opening speed m/s 1.4-1.8
Closing speed m/s 0.4-0.8
Contact closing bounce time ms ≤5
Inter-phase center distance mm 460±2
Asynchronous opening and closing of three-phase circuit breakers ms ≤2
Resistance of each phase conductive circuit μΩ <80
Closing time ms ≤ 100
Opening time ms ≤ 50
Weight Kg 270

External dimensions and installation dimensions (mm)

ZW32-40.5F (M) outdoor high-voltage intelligent (permanent magnet) vacuum circuit breaker

Project inquiry

Tell Us What Your Project Needs

Include the voltage level, quantity, application and destination market for a faster response.