Get a Quote
Home / Products / Indoor High-Voltage / High Voltage Circuit Breaker / Vacuum Circuit Breakers / ZW32-12 outdoor high voltage vacuum circuit breaker
Vacuum Circuit Breakers

ZW32-12 outdoor high voltage vacuum circuit breaker

The ZW32-12 outdoor vacuum circuit breaker (hereinafter referred to as the circuit breaker) is an outdoor power distribution device with a rated voltage of 12 kV and three-phase AC 50 Hz. It is primarily used for interru

Project-focused selection

Support matched to operating conditions and project requirements.

Quality-controlled supply

Clear communication from confirmation through delivery.

Export service

Documentation and shipping support for overseas buyers.

Overview

The ZW32-12 outdoor vacuum circuit breaker (hereinafter referred to as the circuit breaker) is an outdoor power distribution device with a rated voltage of 12 kV and three-phase AC 50 Hz. It is primarily used for interrupting and closing load currents, overload currents, and short-circuit currents in power systems. It is suitable for protection and control in substations, industrial and mining enterprise distribution systems, and in rural areas where power grids are frequently operated. This circuit breaker features a compact size, light weight, condensation resistance, and is maintenance-free, making it suitable for use in harsh climates and polluted environments.

Model meaning

ZW32-12 outdoor high voltage vacuum circuit breaker


Comply with standards

GB1984 "AC high voltage circuit breaker";

GB11022 "Common Technical Requirements for High-voltage Switchgear and Controlgear Standards";

GB311.1-6 "Insulation Coordination of High-voltage Transmission and Transformation Equipment";

GB763 "Heat generation of AC high-voltage electrical appliances during long-term operation";

GB2706 "Test methods for dynamic and thermal stability of AC high-voltage electrical appliances";

GB3309 "Mechanical tests for high-voltage switchgear at room temperature";

DL/T593 "Common Technical Conditions for Ordering High-voltage Switchgear".

Main technical parameters

Project Unit Parameter
Rated voltage KV 12
Rated frequency Hz 50
Rated current A 630
Rated short-circuit breaking current KA 20
Rated peak withstand current (peak) KA 50
Rated short-time withstand current KA 20
Rated short-circuit making current (peak KA 50
Mechanical life 次 10000
Rated short-circuit breaking current breaking times 次 30
Power frequency withstand voltage (1min): (wet) (dry) phase to phase, to ground/break KV 42/48
Lightning impulse withstand voltage (peak) between phases, to ground/break KV 75/85
Secondary circuit 1min power frequency withstand voltage KV 2

Appearance and installation dimensions (mm)

ZW32-12 outdoor high voltage vacuum circuit breaker

Project inquiry

Tell Us What Your Project Needs

Include the voltage level, quantity, application and destination market for a faster response.
询盘表单