Get a Quote
Home / Products / Indoor High-Voltage / High Voltage Circuit Breaker / Vacuum Circuit Breakers / AB-3S-12 outdoor high-voltage fast permanent magnet vacuum circuit breaker
Vacuum Circuit Breakers

AB-3S-12 outdoor high-voltage fast permanent magnet vacuum circuit breaker

The AB-3S-12 series outdoor high-voltage three-phase permanent magnet vacuum circuit breaker is a new generation of pole-mounted intelligent vacuum circuit breaker developed by our company by integrating advanced technol

Project-focused selection

Support matched to operating conditions and project requirements.

Quality-controlled supply

Clear communication from confirmation through delivery.

Export service

Documentation and shipping support for overseas buyers.

Overview

The AB-3S-12 series outdoor high-voltage three-phase permanent magnet vacuum circuit breaker is a new generation of pole-mounted intelligent vacuum circuit breaker developed by our company by integrating advanced technologies from home and abroad, drawing on the strengths of various sources, adopting a brand-new design concept, and utilizing high-tech methods. This product can be used as a switch for the 10kV side of the main transformer and the 10kV outgoing line in a 35kV substation, or as a pole-mounted switch in a distribution network. Combined with various control units produced by our company, it can easily realize control, protection, satellite measurement, and communication, making it the preferred equipment for achieving distribution network automation and miniaturization.

Model Meaning

AB-3S-12 outdoor high-voltage fast permanent magnet vacuum circuit breaker

Usage conditions

◆Ambient temperature: not exceeding 40℃; average daily temperature not exceeding 35℃; minimum ambient air temperature -25℃.

◆Relative humidity: daily average not exceeding 95%, monthly average not exceeding 90%; water vapor pressure: daily average not exceeding 2.2 kPa; monthly average not exceeding 1.8 kPa;

◆Altitude: Not exceeding 2000m;

◆The surrounding area is not significantly contaminated by dust, smoke, corrosive and/or flammable gases, vapors, or salt spray.

◆Vibrations or ground movements from outside the switching and control equipment are negligible;

◆The amplitude of induced electromagnetic interference in the secondary system shall not exceed 1.6kV.

Main technical parameters

Main technical parameters of circuit breaker

Project Unit Parameter
Rated voltage kV 12
Rated insulation level 1-minute power frequency withstand voltage (RMS) kV 42
Lightning impulse withstand voltage (peak value) kV 75
Rated frequency Hz 50
Rated current A 630/1250
Rated short-circuit breaking current kA 20
Rated short-circuit making current (peak value) kA 50
Rated operating sequence Ot1(0.3s)-COt2(3s)-COt2(3s)-CO
Thermally stable current (4S) kA 20
Dynamically stable current (bee value) kA 50
Rated short-circuit current breaking times 次 30
CT ratio 30-1250/1 (5)
Operating power supply voltage V -220(-110)
Creepage distance ≥ 31
Number of machine operations 次 10000
Weight kg 90+40 (quarantine)

Main technical parameters

Mechanical characteristics and technical parameters of circuit breaker after assembly and adjustment

Project Unit Parameter
Contact gap mm 11±1
Contact travel (measures the relative position of the contact spring when it is open or closed) mm 3±0.5
Average closing speed m/s 0.6±0.2
Average tripping speed (per 10mm) m/s 1.0-1.4
Closing time ms 30-50
Opening time ms 30~70
Contact closing bounce time ms ≤2
Asynchronous closing of three-phase contacts ms ≤2
Asynchronous tripping of three-phase contacts ms ≤2
Resistance of each phase conductive circuit μΩ ≤120; with isolation ≤170
Interphase center distance mm 280±2

External dimensions and installation dimensions (mm)

AB-3S-12 outdoor high-voltage fast permanent magnet vacuum circuit breaker