Overview

The GN30-12 type rotary indoor high-voltage disconnect switch is a new type of rotary contact knife disconnect switch. Its main structure consists of two sets of insulators and contacts fixed on the upper and lower planes of a three-phase common base frame. The opening and closing of the switch is achieved by rotating the contact knife.

The GN30-12D type switch is based on the GN30-12 type switch with the addition of a grounding switch, which can meet the needs of different power systems. This product features a compact design, small footprint, strong insulation, and easy installation and adjustment. Its performance meets the requirements of GB1985-89 “AC High Voltage Disconnecting Switches and Grounding Switches,” and is suitable for indoor systems with a rated voltage of 10 kV AC 50Hz and below, used for switching circuits when there is voltage but no load. It can be used in conjunction with high-voltage switchgear or independently.

Model Meaning

GN30-12 Indoor Rotary High Voltage Disconnector

Environmental conditions for use

◆Altitude: Not exceeding 1000m;

◆Air temperature: Upper limit +40℃; Lower limit -10℃

◆Relative humidity: Daily average not exceeding 95%; Monthly average not exceeding 90%;

◆Earthquake intensity: Not exceeding 8 degrees;

◆Contamination level: Location free from severe dust, corrosive chemicals, and explosive substances;

◆Installation location: A location free from frequent and severe vibrations.

Main technical parameters

Product Model Specifications/Items/Parameters GN30-12/400-12.5 GN30-12/630-20 GN30-12/1000-31.5 GN30-12/1250-31.5
GN30-12D/400-12.5 GN30-12D/630-20 GN30-12D/1000-31.5 GN30-12D/1250-31.5
Rated voltage (kV) 2
Rated current (A) 400 630 1000 1250
Thermally stable current (KA) 12.5 20 31.5
Thermal stability time (s) 4
Dynamic stability current (KA) 31.5 50 80
Rated insulation level Lightning impulse voltage (kV) Interspersed, inter-regional 75, fracture 85
Rated insulation level 1-minute power frequency withstand voltage (kV) Interspersed, intersecting, 42, break point 48

External dimensions and installation dimensions (mm)

GN30-12 Indoor Rotary High Voltage Disconnector

GN30-12 GN30-12D
400/630A 1000A 1250A 400/630A 1000A 1250A
A C A C A C A B C A B C A B C
560 315 580 332 580 295 550 610 240 575 615 245 580 600 295

GN30-12 Indoor Rotary High Voltage Disconnector

Selecting GN30-12 Indoor Rotary High-Voltage Disconnector

Before requesting a quotation, confirm switch type and required duty, rated voltage, current and interlocks and installation dimensions and operating mechanism. Send the exact model, quantity and installation details so the configuration and document set can be checked against your project.

Compare the high voltage disconnect switch range, including GN19-12 Indoor High Voltage Disconnector; JN15-12/31.5 Indoor high voltage grounding switch. For drawings and order-specific questions, send your product requirements to GRL.

Project inquiry

Tell Us What Your Project Needs

Include the voltage level, quantity, application and destination market for a faster response.
询盘表单