The GN19-12 series of indoor high-voltage disconnecting switchgear is used in power systems with a rated voltage of 12kV and AC 50Hz and below. It is equipped with the CS6-1 type manual operating mechanism for opening an

Project-focused selection

Support matched to operating conditions and project requirements.

Quality-controlled supply

Clear communication from confirmation through delivery.

Export service

Documentation and shipping support for overseas buyers.

Overview

The GN19-12 series of indoor high-voltage disconnecting switchgear is used in power systems with a rated voltage of 12kV and AC 50Hz and below. It is equipped with the CS6-1 type manual operating mechanism for opening and closing circuits when there is voltage but no load. There are also derivative products such as anti-pollution type, high-altitude type, and type with added live display device.

Model Meaning

GN19-12 Indoor High Voltage Disconnector

Environmental conditions for use

◆Altitude: Not exceeding 1000m;

◆Air temperature: -25℃~+40℃;

◆Relative humidity: Daily average not exceeding 95%, daily average not exceeding 90%;

◆Earthquake intensity: Not exceeding 8 degrees;

◆Installation location: No fire, flammable, explosive, heavily polluted, chemically corrosive, or violently vibrating environments.

Main technical parameters

Model Rated voltage (kV) Rated voltage (V) 4-second thermal stabilization current (kA) Dynamic stability current (kA)
GN19-10(C)400-12.5 12 400 12.5 31.5
GN19-10(C)630-20 12 630 20 50
GN19-10(C)1000-31.5 12 1000 31.5 80
GN19-10(C)1250-40 12 1250 40 100

External dimensions and installation dimensions (mm)

GN19-12 Indoor High Voltage Disconnector

Product Model A B C D
GN19-12/400 450 446 185 4-14×24
GN19-12/630 470 446 185 4-14×24
GN19-12/1000/1250 510 500 196 4-18×28
GN19-12C/400 420 690 185 4-14×24
GN19-12C/630 430 690 185 4-14×24
GN19-12C/1000/1250 470 745 196 4-18×28

The first installation diagram of this switch and the CS6-1 operating mechanism                     The second installation diagram of this switch and the CS6-1 operating mechanism

GN19-12 Indoor High Voltage Disconnector

Assembly drawing of connecting rod

GN19-12 Indoor High Voltage Disconnector

Wiring hole size diagram